Personal tools
You are here: Home Hardware UPS APC SP9617 Firmware upgrade of AP9617 from AOS v2.64 to v3.73

Firmware upgrade of AP9617 from AOS v2.64 to v3.73

Note that it is very important to get the 'Network Management Card v3.7.2 Firmware for Smart-UPS with AP9617/8/9' version of the firmware for a SMART-UPS. Failure to do so will result in the file transfer failing.

Upgrade process

NMC Upgrade Tool v1.2


American Power Conversion               Network Management Card AOS    v3.7.3
(c) Copyright 2004 All Rights Reserved  Smart-UPS & Matrix-UPS APP     v3.7.2
-----------------------------------------------------------------------------

        ********************************************************
        Warning: User name and passord information will displayed
        to the screen in clear text.
        ********************************************************


        IP Address of target to upgrade: 10.20.255.5
        User Name: apc
        Password: apc


        You have entered:
        IP Address: 10.20.255.5
        Username:   apc
        Password:   apc

        1: Continue with upgrade
        2: Enter new parameters
        3: Quit
        Action: 1



        ***************************************************
        Starting Upgrade to 10.20.255.5.
        Checking network connection ...                  OK
        Testing login ...                                OK
        Checking version information ...                 OK
        Attempting to log in to 10.20.255.5 ...         OK
        Loading OS, please wait ...                      OK
        Please wait (2 minutes ) for system restart      OK
        Attempting connection to verify restart          OK
        Attempting to log in to 10.20.255.5 ...         OK
        Loading application, please wait ...             OK
        Please wait (30 seconds) for system restart      OK
        Attempting connection to verify restart          OK


        Verifying 10.20.255.5 upgrade ... OK

        ***************************************************



        *********** Upgrade Summary ***********
        All upgrades completed successfully.


        Warning: A file called 'iplist.txt' exists in this directory
        that may contain user names and passwords in clear text.
        You may want to delete this file if other users have access
        to this directory.


        Thank you for using APC products

        Press <Enter> to exit.

Links

Appendices

Failed file transfer

The file transfer fails if the wrong firmware is attempted to be used/uploaded:

NMC Upgrade Tool v1.2


American Power Conversion               Network Management Card AOS    v3.7.3
(c) Copyright 2004 All Rights Reserved  ISX-PX2                        v3.7.3
-----------------------------------------------------------------------------
        Configuration detected ( iplist.txt ).
        Found 1 upgrade configuration(s)

        1:  Use parameters in configuration file
        2:  Enter new parameters for single upgrade
        3:  Exit Firmware upgrade tool
        Action: 1

        ***************************************************
        Starting Upgrade to 10.20.255.5.
        Checking network connection ...                  OK
        Testing login ...                                OK
        Checking version information ...                 OK
        Attempting to log in to 10.20.255.5 ...         OK
        Loading OS, please wait ...     Firmware download failed.

        *********** Upgrade Summary ***********

        Encountered 1 failures during upgrade.
        View 'result.txt' for details
        Warning: A file called 'iplist.txt' exists in this directory
        that may contain user names and passwords in clear text.
        You may want to delete this file if other users have access
        to this directory.


        Thank you for using APC products

        Press <Enter> to exit.

Old file listing

220 AP9617 Network Management Card AOS v2.6.4 FTP server ready.
User (10.20.255.5:(none)): apc
331 User name okay, need password.
Password:
230 User logged in, proceed.
ftp> dir
200 PORT Command okay.
150 File status okay; about to open data connection.
--wx-wx-wx  1 apc      apc      1310720 Nov 12  2004 apc_hw02_aos_264.bin
drwxrwxrwx  1 apc      apc            0 Nov 12  2004 sec/
--wx-wx-wx  1 apc      apc      2555904 Jan 14  2005 apc_hw02_sumx_261.bin
-r--r--r--  1 apc      apc        34372 Mar 23  2013 event.txt
-r--r--r--  1 apc      apc        54777 Mar 23  2013 data.txt
-rw-rw-rw-  1 apc      apc        32166 Mar 23  2013 config.ini
226 Closing data connection.
ftp: 402 bytes received in 1.67Seconds 0.24Kbytes/sec.

New files

12/09/2011  02:17 p.m.         1,048,576 apc_hw02_aos_202.bin
12/09/2011  02:36 p.m.         1,572,864 apc_hw03_aos_373.bin
12/09/2011  02:36 p.m.         2,031,616 apc_hw03_px2_373.bin
12/09/2011  02:36 p.m.                56 config.txt
23/03/2013  10:15 p.m.                84 foundfir.txt
12/09/2011  02:17 p.m.                26 go.bat
23/03/2013  09:47 p.m.                62 iplist.txt
23/03/2013  10:15 p.m.               536 result.txt
12/09/2011  02:17 p.m.           192,609 upgrd_util.exe
12/09/2011  02:17 p.m.           102,912 winftp32.dll
Document Actions